168 sq ft living room, 10 ft, normal
1.5 tonne AC recommended
Cooling load14,280 BTU/h
Exact1.19 tonne
Buy1 x 1.5 tonne
Load used85 BTU/h per sq ft

Sunny means a west or south facing room with long afternoon sun. A tonne of cooling is 12,000 BTU per hour. The per sq ft figure already allows for the people shown, so change the count only if the room is used differently. Double height treats the volume above 10 ft at partial load, because the occupied zone is what has to be comfortable. Above 3 tonnes, two smaller units cool a room more evenly than one large one.

Assumptions and prices

AC tonnage calculator for Indian rooms, offices and double height spaces

A 150 sq ft bedroom needs a 1 tonne AC and a 250 sq ft living room needs 2 tonnes.

Works out the cooling load from room size, space type, ceiling height, sun exposure, floor, glazing and occupancy, then recommends the AC tonnage sold in India. Double height living rooms and lobbies are handled on the occupied zone rather than the full volume.

How it is worked out: BTU per hour = area x load per sq ft x height factor x sun x floor x glazing, plus extra people; tonnes = BTU / 12,000

Indicative figures, last updated 10 September 2026. Check them against the local source before relying on them.

Questions people ask

What tonnage AC for a 12 by 14 room?

About 1.5 tonnes for a normal bedroom or living room with a 10 ft ceiling on a middle floor. A sunny west-facing room on the top floor pushes it to 2 tonnes.

How is a double height living room different?

Cooling load does not rise in step with the ceiling. Only the lower occupied zone needs to be comfortable, so the calculator adds roughly 45% of the extra height rather than all of it, and allows for warm air collecting at the top. A 20 ft high living room of 360 sq ft works out near 3.7 tonnes, not the 5.3 a straight volume calculation would give.

Why does a gym or restaurant need more than a bedroom?

People, equipment and kitchens all add heat. A gym is taken at 135 BTU per hour per sq ft against 80 for a bedroom, and a restaurant at 125, because bodies and cooking dominate the load.

Common values

Normal sun, middle floor, 10 ft ceiling, typical occupancy. A tonne is 12,000 BTU per hour.
SpaceAreaCooling loadAC size
Bedroom150 sq ft12,000 BTU/h1 tonne
Living room250 sq ft21,250 BTU/h2 tonne
Home office or cabin150 sq ft13,500 BTU/h1.5 tonne
Meeting room200 sq ft21,000 BTU/h2 tonne
Lobby or reception300 sq ft28,500 BTU/h2.5 tonne
Gym300 sq ft40,500 BTU/h3.5 tonne

Built by 256 GRAYS, an interior architecture and 3D visualisation studio in Mumbai.